Paper
4 March 2024 Drum water level control of heat recovery boiler via modified active disturbance rejection control
Author Affiliations +
Proceedings Volume 12981, Ninth International Symposium on Sensors, Mechatronics, and Automation System (ISSMAS 2023); 129814U (2024) https://doi.org/10.1117/12.3014872
Event: 9th International Symposium on Sensors, Mechatronics, and Automation (ISSMAS 2023), 2023, Nanjing, China
Abstract
This paper focuses on the drum water level control of a heat recovery boiler, where drum water level is influenced by many factors such as steam flow and feed water flow. To enhance the control performance of drum water level system, a modified active disturbance rejection control (MADRC) is proposed for the integral system, where the inertial link is compensated by adding a compensation part for the control signal. Then the cascade control structure based on MADRC is applied to the drum water level system. Compared to other comparative controllers, simulation results show that MADRC obtains obvious advantages in terms of tracking performance, disturbance rejection ability, and measure noise rejection ability, with satisfactory robustness.
(2024) Published by SPIE. Downloading of the abstract is permitted for personal use only.
Aimin Gao, Xiaobo Cui, Guoqiang Yu, Jianjun Shu, Xiaolong Yang, Tianhai Zhang, and Xinyu Xiao "Drum water level control of heat recovery boiler via modified active disturbance rejection control", Proc. SPIE 12981, Ninth International Symposium on Sensors, Mechatronics, and Automation System (ISSMAS 2023), 129814U (4 March 2024); https://doi.org/10.1117/12.3014872
Advertisement
Advertisement
RIGHTS & PERMISSIONS
Get copyright permission  Get copyright permission on Copyright Marketplace
KEYWORDS
Control systems

Monte Carlo methods

Device simulation

Design

Gadolinium

Safety

Water

Back to Top